PRODUCTS

Photovoltaic Combined Beauty Change
Photovoltaic power generation as a kind of clean energy production mode, at home and abroad to get rapid development, Z □ S-ZG- □ / □ series combined transformer is to meet the growing photovoltaic power generation power supply requirements, in the company’s production of 35kV combined transformer based on the digesting and absorbing the domestic and foreign advanced technology combined with the domestic demand for self-developed series of products. The product is the transformer, load switch, high-voltage fuse installed in the transformer box, the use of transformer insulating oil as the whole product insulation and heat dissipation medium, the tank adopts a fully sealed structure, with small size and light weight, easy to install and other advantages. Photovoltaic power generation with combined transformer is mainly divided into double winding and axial double split two kinds. Among them, axial double split high-voltage using axial segmented winding, lowvoltage using copper foil winding program, low-voltage two branches can be run separately, can also be run at the same time and parallel operation, in the photovoltaic power generation has been widely used.
Product Overview
Photovoltaic power generation as a kind of clean energy production mode, at home and abroad to get rapid development, Z □ S-ZG- □ / □ series combined transformer is to meet the growing photovoltaic power generation power supply requirements, in the company’s production of 35kV combined transformer based on the digesting and absorbing the domestic and foreign advanced technology combined with the domestic demand for self-developed series of products. The product is the transformer, load switch, high-voltage fuse installed in the transformer box, the use of transformer insulating oil as the whole product insulation and heat dissipation medium, the tank adopts a fully sealed structure, with small size and light weight, easy to install and other advantages. Photovoltaic power generation with combined transformer is mainly divided into double winding and axial double split two kinds. Among them, axial double split high-voltage using axial segmented winding, lowvoltage using copper foil winding program, low-voltage two branches can be run separately, can also be run at the same time and parallel operation, in the photovoltaic power generation has been widely used.

Implementation Standards
GB1094-2013 Power Transformer
GB/T6451-2015《Three-phase oil-immersed power transformer technical parameters and requirements》
Reference:JB/T10217-2013《Combined Transformer》
Conditions Of Use
◆ Altitude:≤4000 meters;
◆ Ambient temperature: Maximum temperature +42℃ , minimum temperature -40℃ ;
◆ Humidity: average daily relative humidity not more than 95%; average monthly relative humidity not more than 90%;
◆ Wind speed: Outdoor wind speed does not exceed 45m/s;
◆ Seismic protection: horizontal acceleration not greater than 0.4m/s2 , vertical acceleration not greater than 0.15m/s2 ;
◆ Installation site inclination: not more than 3°;
◆ Installation environment: the surrounding air is not corrosive, flammable gases and other obvious pollution, the installation site without violent vibration.
In the event that an order for this product exceeds the requirements of the above conditions, please consult with us.